Service Life Data Query
Use various criteria to evaluate the potential service life in different HVAC components in different building environments
|
|
|
Air Distribution - Service Life Data per Above Criteria
[Total # of Matching Buildings: 344] [Total Pieces of Equipment found: 27750]
* Equipment with no units, not shown. View full HVAC Equipment List here
|
|
|
|
|
|
Currently in Service |
|
Replaced |
|
Total Units |
No.of Units |
Equipment Age (years) |
No.of Units |
Age at Removal (years) |
|
Mean |
Median |
Std Dev |
95% C.I. |
Max |
Min |
|
Mean |
Median |
Std Dev |
95% C.I. |
Max |
Min |
Air handling unit, constant volume |
206 |
|
184 |
25.9 |
27.0 |
11.9 |
4.8 |
46.0 |
6.0 |
|
22 |
34.7 |
40.0 |
20.5 |
23.2 |
52.0 |
12.0 |
Air handling unit, dual duct |
20 |
|
20 |
36.5 |
37.0 |
6.6 |
5.3 |
45.0 |
25.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Air handling unit, multizone |
229 |
|
229 |
30.4 |
24.5 |
18.4 |
8.5 |
76.0 |
6.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Air handling unit, single zone |
87 |
|
87 |
21.7 |
18.5 |
12.5 |
7.7 |
44.0 |
10.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Air handling unit, variable air volume |
962 |
|
893 |
18.6 |
20.0 |
8.8 |
1.8 |
47.0 |
-20.0 |
|
69 |
28.2 |
26.0 |
12.4 |
6.3 |
64.0 |
12.0 |
Air handling unit, variable volume, variable temperature |
196 |
|
61 |
20.1 |
21.5 |
9.2 |
5.2 |
34.0 |
4.0 |
|
135 |
12.0 |
12.0 |
n/a |
n/a |
12.0 |
12.0 |
Fan coil unit |
2884 |
|
1605 |
26.8 |
27.0 |
13.8 |
6.0 |
51.0 |
6.0 |
|
1279 |
36.5 |
36.5 |
24.4 |
19.5 |
65.0 |
4.0 |
Heat pump, air-to-air |
1296 |
|
1295 |
14.1 |
14.0 |
5.7 |
4.2 |
20.0 |
3.0 |
|
1 |
17.0 |
17.0 |
n/a |
n/a |
17.0 |
17.0 |
Heat pump, water-to-air, geothermal application |
15090 |
|
11368 |
11.9 |
12.0 |
5.4 |
0.8 |
37.0 |
5.0 |
|
3722 |
27.6 |
25.0 |
13.5 |
3.6 |
69.0 |
8.0 |
Heat pump, water-source |
1484 |
|
1379 |
17.5 |
21.0 |
7.1 |
2.8 |
27.0 |
4.0 |
|
105 |
16.5 |
16.5 |
0.7 |
1.0 |
17.0 |
16.0 |
Heat pump, water-to-water, geothermal application |
28 |
|
28 |
12.0 |
13.0 |
1.7 |
1.9 |
13.0 |
10.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Packaged DX unit, air-cooled |
32 |
|
32 |
14.1 |
15.0 |
7.0 |
4.1 |
27.0 |
6.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Packaged DX unit, rooftop |
220 |
|
215 |
15.6 |
16.0 |
6.8 |
2.1 |
37.0 |
3.0 |
|
5 |
21.3 |
22.0 |
5.4 |
5.3 |
27.0 |
14.0 |
Packaged DX unit, water-cooled |
187 |
|
177 |
14.8 |
17.0 |
9.0 |
4.3 |
35.0 |
4.0 |
|
10 |
22.0 |
22.0 |
n/a |
n/a |
22.0 |
22.0 |
Packaged terminal air conditioner/heat pump |
231 |
|
231 |
27.0 |
27.0 |
14.1 |
19.5 |
37.0 |
17.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Residential furn. and pkg'ed condensing unit/heat pump |
132 |
|
132 |
31.0 |
31.0 |
n/a |
n/a |
31.0 |
31.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Split DX system |
174 |
|
173 |
17.9 |
19.0 |
4.9 |
3.2 |
24.0 |
7.0 |
|
1 |
17.0 |
17.0 |
n/a |
n/a |
17.0 |
17.0 |
Other air distribution equipment |
3089 |
|
3027 |
13.6 |
11.0 |
12.2 |
5.6 |
51.0 |
-1.0 |
|
62 |
20.5 |
20.5 |
6.4 |
8.9 |
25.0 |
16.0 |
|
|