Service Life Data Query
Use various criteria to evaluate the potential service life in different HVAC components in different building environments
|
|
|
Cooling - Service Life Data per Above Criteria
[Total # of Matching Buildings: 287] [Total Pieces of Equipment found: 935]
* Equipment with no units, not shown. View full HVAC Equipment List here
|
|
|
|
|
|
Currently in Service |
|
Replaced |
|
Total Units |
No.of Units |
Equipment Age (years) |
No.of Units |
Age at Removal (years) |
|
Mean |
Median |
Std Dev |
95% C.I. |
Max |
Min |
|
Mean |
Median |
Std Dev |
95% C.I. |
Max |
Min |
No cooling plant |
4 |
|
2 |
5.0 |
5.0 |
n/a |
n/a |
5.0 |
5.0 |
|
2 |
20.0 |
20.0 |
n/a |
n/a |
20.0 |
20.0 |
Chiller, absorption, indirect-fired, single-stage |
6 |
|
6 |
38.0 |
38.0 |
0.0 |
0.0 |
38.0 |
38.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Chiller, air-cooled reciprocating |
16 |
|
15 |
24.0 |
28.5 |
14.3 |
8.1 |
37.0 |
4.0 |
|
1 |
11.0 |
11.0 |
n/a |
n/a |
11.0 |
11.0 |
Chiller, air-cooled rotary (screw) |
9 |
|
8 |
12.3 |
8.5 |
10.3 |
8.2 |
32.0 |
5.0 |
|
1 |
23.0 |
23.0 |
n/a |
n/a |
23.0 |
23.0 |
Chiller, centrifugal |
239 |
|
209 |
17.6 |
18.0 |
8.2 |
1.5 |
41.0 |
3.0 |
|
30 |
25.2 |
25.0 |
7.6 |
3.3 |
42.0 |
7.0 |
Chiller, heat recovery, centrifugal |
2 |
|
2 |
21.5 |
21.5 |
4.9 |
6.8 |
25.0 |
18.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Chiller, water-cooled reciprocating |
9 |
|
9 |
20.6 |
17.0 |
11.2 |
8.3 |
35.0 |
6.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Chiller, water-cooled rotary (screw) |
5 |
|
5 |
11.0 |
11.0 |
7.1 |
9.8 |
16.0 |
6.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
District cooling |
8 |
|
3 |
7.3 |
8.0 |
1.2 |
1.4 |
8.0 |
6.0 |
|
5 |
36.0 |
36.0 |
22.6 |
31.3 |
52.0 |
20.0 |
Heat exchanger, horizontal ground |
7 |
|
7 |
10.9 |
11.0 |
2.0 |
1.5 |
13.0 |
8.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Heat exchanger, horizontal (trench) ground |
8 |
|
7 |
14.1 |
13.0 |
2.7 |
2.0 |
20.0 |
12.0 |
|
1 |
17.0 |
17.0 |
n/a |
n/a |
17.0 |
17.0 |
Heat exchanger, ground water, aquifers |
37 |
|
30 |
23.5 |
18.5 |
13.1 |
4.7 |
53.0 |
7.0 |
|
7 |
32.0 |
21.0 |
27.8 |
20.6 |
88.0 |
8.0 |
Heat exchanger, ground water, standing column well |
6 |
|
4 |
11.8 |
12.0 |
1.3 |
1.3 |
13.0 |
10.0 |
|
2 |
51.5 |
51.5 |
34.6 |
48.0 |
76.0 |
27.0 |
Heat exchanger, potable water |
1 |
|
1 |
8.0 |
8.0 |
n/a |
n/a |
8.0 |
8.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Heat exchanger, vertical bore |
195 |
|
142 |
11.5 |
11.0 |
5.2 |
0.9 |
37.0 |
-1.0 |
|
53 |
27.1 |
25.0 |
13.8 |
3.7 |
69.0 |
4.0 |
Heat exchanger, surface water, closed loop |
2 |
|
2 |
11.5 |
11.5 |
6.4 |
8.9 |
16.0 |
7.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Municipal water plant |
7 |
|
7 |
10.3 |
10.0 |
2.2 |
1.6 |
13.0 |
7.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Other cooling equipment |
369 |
|
365 |
16.3 |
20.0 |
10.2 |
5.0 |
34.0 |
-1.0 |
|
4 |
20.5 |
20.5 |
5.2 |
5.1 |
25.0 |
16.0 |
|
|