Database Main Page
Project Summary
Preferences
Model Your Building
Service Life Data
by System Type
Maintenance Cost Data
by All Options
by Region
by State
by BOMA Class
by Function
by Size
HVAC Equipment List
Related Documentation
Download Database
Submit HVAC Data
Service Life Data Query
Use various criteria to evaluate the potential service life in
different HVAC components in different building environments

Region region details
State
Function
Size (sf)
Age (years)
Height (stories)
BOMA Class
Location
SYSTEM TYPE
Equipment Type
reset

Download Dataset [excel]

Cooling - Service Life Data per Above Criteria
[Total # of Matching Buildings: 287]
[Total Pieces of Equipment found: 935]
* Equipment with no units, not shown. View full HVAC Equipment List here
Currently in Service Replaced
Total
Units
No.of
Units
Equipment Age (years)
No.of
Units
Age at Removal (years)
Mean
Median
Std Dev
95% C.I.
Max
Min
Mean
Median
Std Dev
95% C.I.
Max
Min
No cooling plant
4
2
5.0
5.0
n/a
n/a
5.0
5.0
2
20.0
20.0
n/a
n/a
20.0
20.0
Chiller, absorption, indirect-fired, single-stage
6
6
38.0
38.0
0.0
0.0
38.0
38.0
0
n/a
n/a
n/a
n/a
n/a
n/a
Chiller, air-cooled reciprocating
16
15
24.0
28.5
14.3
8.1
37.0
4.0
1
11.0
11.0
n/a
n/a
11.0
11.0
Chiller, air-cooled rotary (screw)
9
8
12.3
8.5
10.3
8.2
32.0
5.0
1
23.0
23.0
n/a
n/a
23.0
23.0
Chiller, centrifugal
239
209
17.6
18.0
8.2
1.5
41.0
3.0
30
25.2
25.0
7.6
3.3
42.0
7.0
Chiller, heat recovery, centrifugal
2
2
21.5
21.5
4.9
6.8
25.0
18.0
0
n/a
n/a
n/a
n/a
n/a
n/a
Chiller, water-cooled reciprocating
9
9
20.6
17.0
11.2
8.3
35.0
6.0
0
n/a
n/a
n/a
n/a
n/a
n/a
Chiller, water-cooled rotary (screw)
5
5
11.0
11.0
7.1
9.8
16.0
6.0
0
n/a
n/a
n/a
n/a
n/a
n/a
District cooling
8
3
7.3
8.0
1.2
1.4
8.0
6.0
5
36.0
36.0
22.6
31.3
52.0
20.0
Heat exchanger, horizontal ground
7
7
10.9
11.0
2.0
1.5
13.0
8.0
0
n/a
n/a
n/a
n/a
n/a
n/a
Heat exchanger, horizontal (trench) ground
8
7
14.1
13.0
2.7
2.0
20.0
12.0
1
17.0
17.0
n/a
n/a
17.0
17.0
Heat exchanger, ground water, aquifers
37
30
23.5
18.5
13.1
4.7
53.0
7.0
7
32.0
21.0
27.8
20.6
88.0
8.0
Heat exchanger, ground water, standing column well
6
4
11.8
12.0
1.3
1.3
13.0
10.0
2
51.5
51.5
34.6
48.0
76.0
27.0
Heat exchanger, potable water
1
1
8.0
8.0
n/a
n/a
8.0
8.0
0
n/a
n/a
n/a
n/a
n/a
n/a
Heat exchanger, vertical bore
195
142
11.5
11.0
5.2
0.9
37.0
-1.0
53
27.1
25.0
13.8
3.7
69.0
4.0
Heat exchanger, surface water, closed loop
2
2
11.5
11.5
6.4
8.9
16.0
7.0
0
n/a
n/a
n/a
n/a
n/a
n/a
Municipal water plant
7
7
10.3
10.0
2.2
1.6
13.0
7.0
0
n/a
n/a
n/a
n/a
n/a
n/a
Other cooling equipment
369
365
16.3
20.0
10.2
5.0
34.0
-1.0
4
20.5
20.5
5.2
5.1
25.0
16.0