[Total # of Matching Buildings: 111] [Total Pieces of Equipment found: 261]
* Equipment with no units, not shown. View full HVAC Equipment List here
|
|
|
|
|
|
Currently in Service |
|
Replaced |
|
Total Units |
No.of Units |
Equipment Age (years) |
No.of Units |
Age at Removal (years) |
|
Mean |
Median |
Std Dev |
95% C.I. |
Max |
Min |
|
Mean |
Median |
Std Dev |
95% C.I. |
Max |
Min |
Condenser, air-cooled |
13 |
|
11 |
16.0 |
10.0 |
13.3 |
11.7 |
37.0 |
5.0 |
|
2 |
20.0 |
20.0 |
n/a |
n/a |
20.0 |
20.0 |
Condenser, evaporative |
5 |
|
5 |
22.3 |
18.5 |
10.0 |
9.8 |
37.0 |
15.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Condenser, water-cooled |
3 |
|
3 |
21.0 |
21.0 |
n/a |
n/a |
21.0 |
21.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Cooler, closed circuit |
7 |
|
7 |
8.8 |
6.5 |
5.7 |
5.6 |
17.0 |
5.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Cooling tower, ceramic |
3 |
|
3 |
27.5 |
27.5 |
0.7 |
1.0 |
28.0 |
27.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Cooling tower, fiberglass |
2 |
|
2 |
25.0 |
25.0 |
n/a |
n/a |
25.0 |
25.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Cooling tower, metal |
188 |
|
162 |
17.4 |
17.5 |
9.5 |
1.8 |
42.0 |
3.0 |
|
26 |
19.8 |
17.5 |
7.0 |
3.2 |
35.0 |
12.0 |
Cooling tower, wood |
8 |
|
8 |
24.5 |
24.5 |
1.3 |
1.3 |
26.0 |
23.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Heat exchanger, condenser water |
1 |
|
1 |
27.0 |
27.0 |
n/a |
n/a |
27.0 |
27.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Heat exchanger, water-to-water |
1 |
|
1 |
23.0 |
23.0 |
n/a |
n/a |
23.0 |
23.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Other heat rejection equipment |
30 |
|
30 |
8.0 |
8.0 |
n/a |
n/a |
8.0 |
8.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
|
|