Service Life Data Query
Use various criteria to evaluate the potential service life in different HVAC components in different building environments
|
|
|
Cooling Pump - Service Life Data per Above Criteria
[Total # of Matching Buildings: 79] [Total Pieces of Equipment found: 361]
* Equipment with no units, not shown. View full HVAC Equipment List here
|
|
|
|
|
|
Currently in Service |
|
Replaced |
|
Total Units |
No.of Units |
Equipment Age (years) |
No.of Units |
Age at Removal (years) |
|
Mean |
Median |
Std Dev |
95% C.I. |
Max |
Min |
|
Mean |
Median |
Std Dev |
95% C.I. |
Max |
Min |
Centrifugal pump, close-coupled, end-suction |
89 |
|
89 |
18.8 |
20.0 |
6.7 |
2.4 |
42.0 |
7.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Centrifugal pump, frame-mounted, end-suction |
111 |
|
111 |
19.1 |
21.0 |
9.2 |
3.0 |
35.0 |
3.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Centrifugal pump, split-case, multistage pump |
12 |
|
7 |
19.0 |
26.0 |
13.9 |
15.7 |
28.0 |
3.0 |
|
5 |
42.0 |
42.0 |
n/a |
n/a |
42.0 |
42.0 |
Centrifugal pump, split-case, single stage |
133 |
|
133 |
20.6 |
21.0 |
9.2 |
2.4 |
38.0 |
5.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Centrifugal pump, vertical in-line |
10 |
|
10 |
17.9 |
18.0 |
6.8 |
5.0 |
32.0 |
12.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Condensate pump |
7 |
|
4 |
6.3 |
5.0 |
4.2 |
4.8 |
11.0 |
3.0 |
|
3 |
23.5 |
23.5 |
3.5 |
4.9 |
26.0 |
21.0 |
|
|