Service Life Data Query
Use various criteria to evaluate the potential service life in different HVAC components in different building environments
|
|
|
Heating - Service Life Data per Above Criteria
[Total # of Matching Buildings: 262] [Total Pieces of Equipment found: 4794]
* Equipment with no units, not shown. View full HVAC Equipment List here
|
|
|
|
|
|
Currently in Service |
|
Replaced |
|
Total Units |
No.of Units |
Equipment Age (years) |
No.of Units |
Age at Removal (years) |
|
Mean |
Median |
Std Dev |
95% C.I. |
Max |
Min |
|
Mean |
Median |
Std Dev |
95% C.I. |
Max |
Min |
No heating plant |
2 |
|
2 |
26.5 |
26.5 |
4.9 |
6.8 |
30.0 |
23.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Boiler, cast iron |
12 |
|
12 |
23.6 |
24.0 |
9.1 |
5.9 |
35.0 |
4.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Boiler, electric hot water |
4 |
|
4 |
19.3 |
22.0 |
7.6 |
7.4 |
25.0 |
8.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Boiler, steel fire-tube, forced draft, hot water |
12 |
|
10 |
14.0 |
12.0 |
7.2 |
6.3 |
23.0 |
7.0 |
|
2 |
25.0 |
25.0 |
n/a |
n/a |
25.0 |
25.0 |
Boiler, steel fire-tube, forced draft, steam |
10 |
|
10 |
36.8 |
38.0 |
9.0 |
7.9 |
46.0 |
23.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Boiler, steel fire-tube, natural draft, hot water |
11 |
|
11 |
17.5 |
17.0 |
4.1 |
3.3 |
24.0 |
12.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Boiler, steel water-tube, forced draft, hot water |
56 |
|
42 |
19.6 |
15.0 |
13.9 |
4.8 |
51.0 |
4.0 |
|
14 |
22.6 |
21.0 |
9.4 |
7.0 |
33.0 |
10.0 |
Boiler, steel water-tube, forced draft, steam |
4 |
|
4 |
37.0 |
37.0 |
1.0 |
1.1 |
38.0 |
36.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Boiler, steel water-tube, natural draft, hot water |
47 |
|
35 |
17.9 |
19.5 |
12.1 |
5.6 |
40.0 |
3.0 |
|
12 |
18.0 |
18.5 |
4.9 |
3.9 |
23.0 |
11.0 |
Chiller, heat recovery, centrifugal |
2 |
|
1 |
25.0 |
25.0 |
n/a |
n/a |
25.0 |
25.0 |
|
1 |
65.0 |
65.0 |
n/a |
n/a |
65.0 |
65.0 |
District heating |
9 |
|
9 |
29.2 |
37.0 |
16.4 |
10.7 |
57.0 |
6.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Heat exchanger, horizontal ground |
7 |
|
7 |
10.9 |
11.0 |
2.0 |
1.5 |
13.0 |
8.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Heat exchanger, horizontal (trench) ground |
9 |
|
8 |
13.8 |
13.0 |
2.7 |
1.9 |
20.0 |
11.0 |
|
1 |
17.0 |
17.0 |
n/a |
n/a |
17.0 |
17.0 |
Heat exchanger, ground water, aquifers |
35 |
|
28 |
23.2 |
18.5 |
12.8 |
4.7 |
53.0 |
7.0 |
|
7 |
32.0 |
21.0 |
27.8 |
20.6 |
88.0 |
8.0 |
Heat exchanger, ground water, standing column well |
6 |
|
4 |
11.8 |
12.0 |
1.3 |
1.3 |
13.0 |
10.0 |
|
2 |
51.5 |
51.5 |
34.6 |
48.0 |
76.0 |
27.0 |
Heat exchanger, vertical bore |
214 |
|
144 |
11.3 |
11.0 |
5.7 |
1.0 |
37.0 |
-16.0 |
|
70 |
27.6 |
25.0 |
13.6 |
3.7 |
69.0 |
4.0 |
Heat exchanger, surface water, closed loop |
2 |
|
2 |
11.5 |
11.5 |
6.4 |
8.9 |
16.0 |
7.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Municipal water plant |
6 |
|
6 |
10.7 |
11.0 |
2.2 |
1.8 |
13.0 |
7.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Other heating equipment |
4234 |
|
4192 |
15.1 |
16.0 |
9.5 |
4.5 |
35.0 |
-1.0 |
|
42 |
23.2 |
25.0 |
7.5 |
6.6 |
34.0 |
16.0 |
|
|