Service Life Data Query
Use various criteria to evaluate the potential service life in different HVAC components in different building environments
|
|
|
Heating Pump - Service Life Data per Above Criteria
[Total # of Matching Buildings: 43] [Total Pieces of Equipment found: 122]
* Equipment with no units, not shown. View full HVAC Equipment List here
|
|
|
|
|
|
Currently in Service |
|
Replaced |
|
Total Units |
No.of Units |
Equipment Age (years) |
No.of Units |
Age at Removal (years) |
|
Mean |
Median |
Std Dev |
95% C.I. |
Max |
Min |
|
Mean |
Median |
Std Dev |
95% C.I. |
Max |
Min |
Centrifugal pump, close-coupled, end-suction |
38 |
|
38 |
17.7 |
17.5 |
10.4 |
4.8 |
42.0 |
4.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Centrifugal pump, frame-mounted, end-suction |
55 |
|
55 |
24.9 |
21.5 |
12.4 |
5.4 |
46.0 |
5.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Centrifugal pump, split-case, multistage pump |
6 |
|
6 |
22.0 |
21.0 |
12.5 |
14.1 |
35.0 |
10.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Centrifugal pump, split-case, single stage |
11 |
|
11 |
27.7 |
38.0 |
16.0 |
12.8 |
38.0 |
6.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Centrifugal pump, vertical in-line |
8 |
|
8 |
25.3 |
21.0 |
8.4 |
9.5 |
35.0 |
20.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Other pump type |
4 |
|
4 |
17.0 |
17.0 |
n/a |
n/a |
17.0 |
17.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
|
|