Service Life Data Query
Use various criteria to evaluate the potential service life in different HVAC components in different building environments
|
|
|
Control - Service Life Data per Above Criteria
[Total # of Matching Buildings: 321] [Total Pieces of Equipment found: 2469]
* Equipment with no units, not shown. View full HVAC Equipment List here
|
|
|
|
|
|
Currently in Service |
|
Replaced |
|
Total Units |
No.of Units |
Equipment Age (years) |
No.of Units |
Age at Removal (years) |
|
Mean |
Median |
Std Dev |
95% C.I. |
Max |
Min |
|
Mean |
Median |
Std Dev |
95% C.I. |
Max |
Min |
Energy mgmt. system, all electronic components |
101 |
|
77 |
12.5 |
11.0 |
7.0 |
1.6 |
37.0 |
5.0 |
|
24 |
22.1 |
18.0 |
16.3 |
6.5 |
69.0 |
8.0 |
Energy mgmt. system, all pneumatic components |
20 |
|
19 |
16.2 |
17.0 |
7.2 |
3.2 |
28.0 |
6.0 |
|
1 |
11.0 |
11.0 |
n/a |
n/a |
11.0 |
11.0 |
Energy mgmt. system, direct digital controls |
146 |
|
115 |
10.9 |
10.0 |
5.2 |
1.0 |
26.0 |
-6.0 |
|
31 |
24.7 |
25.0 |
13.4 |
4.7 |
52.0 |
4.0 |
Energy mgmt. system, hybrid system with elec./pneumatic components |
133 |
|
101 |
13.6 |
13.0 |
5.3 |
1.0 |
26.0 |
3.0 |
|
32 |
16.7 |
14.0 |
11.7 |
4.1 |
48.0 |
1.0 |
Manual control |
7 |
|
6 |
14.3 |
11.5 |
11.3 |
9.0 |
37.0 |
7.0 |
|
1 |
76.0 |
76.0 |
n/a |
n/a |
76.0 |
76.0 |
Pneumatic controls |
19 |
|
19 |
35.0 |
37.0 |
7.7 |
3.8 |
51.0 |
17.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Thermostats, electric |
1 |
|
1 |
22.0 |
22.0 |
n/a |
n/a |
22.0 |
22.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Time clock |
18 |
|
16 |
9.3 |
4.0 |
10.5 |
10.3 |
25.0 |
4.0 |
|
2 |
20.0 |
20.0 |
n/a |
n/a |
20.0 |
20.0 |
Other control system |
38 |
|
30 |
15.0 |
13.0 |
7.7 |
2.8 |
42.0 |
6.0 |
|
8 |
32.6 |
25.0 |
24.9 |
17.3 |
88.0 |
11.0 |
|
|