Service Life Data Query
Use various criteria to evaluate the potential service life in different HVAC components in different building environments
|
|
|
Miscellaneous - Service Life Data per Above Criteria
[Total # of Matching Buildings: 108] [Total Pieces of Equipment found: 2254]
* Equipment with no units, not shown. View full HVAC Equipment List here
|
|
|
|
|
|
Currently in Service |
|
Replaced |
|
Total Units |
No.of Units |
Equipment Age (years) |
No.of Units |
Age at Removal (years) |
|
Mean |
Median |
Std Dev |
95% C.I. |
Max |
Min |
|
Mean |
Median |
Std Dev |
95% C.I. |
Max |
Min |
Baseboard/Finned Tube Radiation |
100 |
|
100 |
18.1 |
21.0 |
7.8 |
4.4 |
25.0 |
4.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Cogeneration |
2 |
|
2 |
15.0 |
15.0 |
n/a |
n/a |
15.0 |
15.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Computer room air conditioning unit, chilled water |
268 |
|
268 |
17.7 |
20.5 |
7.8 |
4.8 |
30.0 |
5.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Computer room air conditioning unit, water-cooled DX compressor |
94 |
|
91 |
13.6 |
13.0 |
6.6 |
3.0 |
23.0 |
3.0 |
|
3 |
14.0 |
14.0 |
5.7 |
7.9 |
18.0 |
10.0 |
Domestic hot water heater, electric |
309 |
|
273 |
15.5 |
17.5 |
8.2 |
2.0 |
34.0 |
-1.0 |
|
36 |
11.8 |
12.0 |
5.4 |
2.5 |
26.0 |
2.0 |
Domestic hot water heater, natural gas |
26 |
|
20 |
13.1 |
8.5 |
8.9 |
5.0 |
35.0 |
5.0 |
|
6 |
15.0 |
15.0 |
7.0 |
7.9 |
22.0 |
8.0 |
Exhaust fan |
226 |
|
222 |
20.2 |
21.0 |
8.4 |
2.1 |
46.0 |
-1.0 |
|
4 |
18.3 |
16.0 |
6.8 |
7.7 |
26.0 |
13.0 |
Fresh Air Units |
43 |
|
41 |
18.9 |
21.0 |
7.5 |
2.8 |
34.0 |
5.0 |
|
2 |
16.0 |
16.0 |
n/a |
n/a |
16.0 |
16.0 |
Fume Hoods/Cabinets |
1 |
|
1 |
22.0 |
22.0 |
n/a |
n/a |
22.0 |
22.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Heat exchanger, plate and frame |
11 |
|
11 |
13.1 |
8.0 |
8.2 |
5.4 |
25.0 |
5.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Heat exchanger, heat pipe |
2 |
|
2 |
5.0 |
5.0 |
n/a |
n/a |
5.0 |
5.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Heat exchanger, heat wheel |
2 |
|
1 |
-1.0 |
-1.0 |
n/a |
n/a |
-1.0 |
-1.0 |
|
1 |
42.0 |
42.0 |
n/a |
n/a |
42.0 |
42.0 |
Heat exchanger, hot water |
3 |
|
3 |
38.0 |
38.0 |
n/a |
n/a |
38.0 |
38.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Heat recovery unit, air-to-air |
2 |
|
2 |
10.0 |
10.0 |
n/a |
n/a |
10.0 |
10.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Humidifiers |
3 |
|
1 |
7.0 |
7.0 |
n/a |
n/a |
7.0 |
7.0 |
|
2 |
23.0 |
23.0 |
n/a |
n/a |
23.0 |
23.0 |
Perimeter heating, supplemental heating |
810 |
|
810 |
24.2 |
23.0 |
7.1 |
4.6 |
38.0 |
15.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Refrigeration equipment (ice machines, walk-in coolers/freezers) |
13 |
|
12 |
10.3 |
10.5 |
8.4 |
8.2 |
18.0 |
2.0 |
|
1 |
42.0 |
42.0 |
n/a |
n/a |
42.0 |
42.0 |
Smoke control |
15 |
|
15 |
17.5 |
17.5 |
3.5 |
4.9 |
20.0 |
15.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Unit heater, electric |
138 |
|
131 |
13.5 |
10.0 |
8.4 |
3.7 |
29.0 |
3.0 |
|
7 |
13.0 |
12.5 |
8.1 |
7.9 |
21.0 |
6.0 |
Unit heater, natural gas |
12 |
|
12 |
23.0 |
23.5 |
1.7 |
1.4 |
25.0 |
21.0 |
|
0 |
n/a |
n/a |
n/a |
n/a |
n/a |
n/a |
Other miscellaneous equipment |
163 |
|
157 |
19.4 |
20.0 |
11.2 |
3.5 |
46.0 |
-1.0 |
|
6 |
18.0 |
16.0 |
7.2 |
6.3 |
26.0 |
8.0 |
Dehumidifier, solid dessicant |
2 |
|
1 |
-1.0 |
-1.0 |
n/a |
n/a |
-1.0 |
-1.0 |
|
1 |
42.0 |
42.0 |
n/a |
n/a |
42.0 |
42.0 |
|
|